OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 58
INP Name Input Name: Name of Sensor Input specified to identify function of Sensor. The name USER
indicates a User-Defined Sensor Name. See next setting for User-Defined Name.
Entry Type: select list
Range Limits: See Below Table
Default/Initialized value: User
User
User-Defined
Sump
Sump
Piping
Piping
Contn
Containment
DbwaLL
Double-Wall
Dike
Dike
LEAk
Leak
Resvor
Reservoir
WELL
Well
genrtr
Generator
Water
Water
OiL
Oil
Vault
Vault
Hi res
High Reservoir
Lo RES
Low Reservoir
High
High
Hihigh
High-High
Lo
Low
LoLo
Low-Low
trbinE
Turbine
Dispan
Dispenser Pan
User Name User-Defined Input Name: A 6-character alphanumeric name entered via TMSComm. Note that
this is a context sensitive setting that only appears if the Sensor Input Name is set for User
Entry Type: select list
Range Limits: 6-character alphanumeric. Must be entered via TMSComm.
Default/Initialized value: Input
FauLt En Fault Enable: Must be enabled for sensors with a -F suffix in the model number. The Fault-
Detection feature, also referred to as Supervised Wiring, enables the TMS to monitor the field
wiring for open or short circuits, preventing the TMS from determining the alarm state of the
sensor.
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: no
normaLLy Normal Contact State: The normal state of the Sensor wired to the Sensor Input.
Entry Type: select list
Range Limits: Close, Open
Default/Initialized value: CLOSE
Associate Associate with Tank: Supplements the Sensor Name for the purpose of locating the sensor by
identifying the Tank Channel the sensor is supporting. Leak Sensors enabled as Alarms that
are Associated with a Tank Channel may be represented on the ETD1000 by activating the
Leak light and integrated horn.
Entry Type: select list
Range Limits: Tank NO: Sensor NOT Associated with Tank Channel
Tank 1-12 (TMS3000), Tank 1-2 (TMS2000)
Default/Initialized value: tnk no
Associate Associate with Dispenser: Supplements the Sensor Name for the purpose of locating the sensor
by identifying the Dispenser Pan the sensor is installed in.
Entry Type: select list
Range Limits: Dispenser NO: Sensor NOT Associated with Dispenser Pan
Dispenser 1-40
Default/Initialized value: dsp no
Return Return: Press EDIT (TEST) to exit Sensor Input submenu.
Note: Press STEP (MODE) to return to top of Sensor Input submenu showing Sensr En
(Sensor Enable)