OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 38
2.4.3.2 SYSTEM CONFIGURATION – TANK
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
tank Tank: Contains Tank Channel specific settings including tank geometry, alarm setpoints, tank
identification, and other tank customization options. The Group ID shown corresponds to the
hardware Tank Channel and NOT the Tank ID.
tank En Tank Channel Enable: Requires level-gauging probe connected to the specific tank channel to
be enabled.
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: no
tank Name Tank Name: Select a name from a predefined list. If a User-Defined name is assigned to the
Tank Channel via TMSComm, the Tank Name is shown as User.
Entry Type: select list
Range Limits: See below table
Default/Initialized value: gas