OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 55
2.4.3.10 SYSTEM CONFIGURATION CC INPUT
Config
Header Header General System Settings
tank Tank Tank Channel specific including geometry and SetPoints
Probe Probe Level Gauging Probe settings
ReLy tank Relay Tank Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test Setup
AnaLogout Analog Outputs
cc inp Non-Hazardous Contact Closure (CC) Input: The behavior of each CC Input can be configured to
support a variety of applications. These include remote Testing and Acknowledgment of remote
Alarms as well as more advanced Logic AND Gate functions. See below for complete details. The
Group ID shown corresponds to the CC Input Number.
cc EnabLe CC Input Enable: A variety of options are available for enabling a CC Input to support a number
of different applications. Each choice is described below.
Entry Type: Select list (See table below)
Range Limits: Off: Disabled
Relay: Used as a control input for manipulating Relay Outputs or to support
Auto In-Tank Leak Test Mode
Gate: AND Logic Gate created from both the CC Input and another system
condition that are assigned to affect the same Relay Output.
Alarm: Displays an Alarm on TMS and is recorded in the Alarm Log.
Acknowledge: Returns assigned Relay Outputs to their Normal Contact
State.
Line Pass: Accepts signals from LS300 (2
nd
Generation) to report a passing
Line Leak Test.
Front Panel Ack: An external signal, typically from an automation system,
used to acknowledge the integrated horn on the front panel of the TMS.
Trigger Groups: Part of a Pump Auto Select feature where the TMS would
select the pump associated with the tank with the greatest volume. Contact
Pneumercator for a separate application document for the Pump Auto Select
feature.
Default/Initialized value: OFF
OFF
Off
rELAy
Relay
gAtE
Gate
ALArM
Alarm
Ack
Acknowledge
LPASS
Line Pass
FPAck
Front Panel Ack
trig-A
Trigger Group A
trig-b
Trigger Group B
trig-C
Trigger Group C
trig-d
Trigger Group D
trig-E
Trigger Group E
trig-F
Trigger Group F

Table of Contents