OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 64
2.4.3.15 SYSTEM CONFIGURATION – DIAL OUT
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
diaL out Auto-Dial out – Setup for selected Alarms or Tank information: The TMS can initiate contact using
an internal modem or faxmodem to provide notifications of Alarm conditions and scheduled
inventory updates. Up to five sets of conditions may be defined, each with a different phone number
and destination device. The Group ID indicates the set number. The TMS will make a total of five
dialout attempts per condition. The dialout sequence may be aborted by clearing the Dialout memory
in the Init Data submenu.
teL LOCAL Telephone Number: Up to 21 digits available for defining the dial-out sequence including the
teL Area telephone number and any required prefix or suffix details. Complete 21 digit value formed
teL Area2 as Tel Area 2 + Tel Area + Tel Local, each with a 7 digit maximum.
Entry Type: 7-digit numeric each
Range Limits: 0-9, P (Pause), _ (Blank)
Default/Initialized value: _______
Line type Line Type: The type of receiving device connected to the telephone line that the TMS will be
communicating with.
Entry Type: Select list
Range Limits: dAtA (Data): Transfer data to computer running Autopolling
FCS (Facsimile): Send a fax to a fax machine (requires faxmodem)
tty (TTY): TeleType text only transmission.
nPAgEr (NPager): Numeric Pager
Default/Initialized value: data