OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 36
SP1 LED Product SetPoint LED assignment: (6 Product SetPoint Firmware Only: Vxx01xx). Selects
SP2 LED which of the six Product SetPoints are mapped to which of the three SP LEDs on the TMS
SP3 LED Display. A Product SetPoint is considered to be an Alarm condition when it is associated with
an LED. The remaining three Product SetPoints may be used to control Relay Outputs and are
represented across all communications interfaces.
Entry Type: select list
Range Limits: Critical High, High High, High, Low, Low Low, Critical Low
Default/Initialized value: SP1 LED: HiHigh: High High
SP2 LED: High: High
SP3 LED: Lo: Low
SALE En Bulk Sales Enable: Enables tracking of Product Sales from the tanks being monitored. A sale
is defined as a loss of Product during normal hours of operation. Sales are logged in the Sales
Log provided they meet the Minimum Log Volume requirements defined in the
Configuration/Probe submenu
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: no
HorndeLay Horn Autosilence Delay: The integrated horn can be automatically acknowledged after a time
delay ranging from 1-9 minutes. This feature is disabled by selecting NONE.
Entry Type: select list
Range Limits: None, 1-9
Default/Initialized value: none
AutoPrint Auto Print Enable: Allows the TMS to generate automatic printouts for Alarms, Events, liquid
transactions, and other optional reports enabled in the TMS. Disabling this feature prevents ALL
system-generated printouts from occurring. Manual printing is unaffected by this feature.
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: yes
LeakPrint Leak Print Mode: Determines when a completed In-Tank Leak Test generates an automatic
printout. The default of Pass-Fail generates a printout for ANY completed test.
Entry Type: select list
Range Limits: Pass-Fail, Fail Only
Default/Initialized value: pass-faiL
MonthLy Monthly Status Report Enable: An automatic printout generated at midnight on the first of every
month that contains a complete alarm status report for all Tanks/Probes and Leak/Point Level
Sensors.
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: no
ULL Limit Percent Ullage Limit: The maximum fill point defined as a percentage of total tank capacity. The
Ullage displayed on the real-time display and contained in system logs will be calculated based
on this threshold and is displayed using volume units of gallons/liters
Entry Type: select list
Range Limits: 90, 95, 100, 85
Default/Initialized value: 90
Dst EnabL Daylight Savings Time Enable: The TMS can automatically adjust its internal clock based on
the 2007 U.S. Daylight Savings Time rules.
Entry Type: select list
Range Limits: No, Yes
Default/Initialized value: no