OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 33
2.4.3 SYSTEM CONFIGURATION
ACCESS
Log
LEAK test
Config
Clock
Init data
Return
In view mode depressing Test button first, then Mode and holding both buttons momentarily will increment the
TMS into the ACCESS MODE displaying the main menu beginning as follows with Log. Pressing the Test button
again will increment to the LEAk test menu and then to the Config menu. Once in Config pressing the MODE
button will open the Header submenu.
The Config menu is used to review, edit, or print system configuration data.
Three types of entries require the user to input programming data when configuring the TMS menus. It is mentioned
here, to help the user interpret data displayed in the CONFIG menus. This information below will be explained again
in the CLOCK section of the manual.
The Entry Type: User programs either a numeric value or chooses from a predefined list of terms.
The Range Limits: User selects and enters a numeric value within a fixed boundary, set by the system.
The Default/Initialized value: If not user programmed, this entry, value or term, will be set by the system.
The user may increment through the following submenus in CONFIG to review data in the following categories.
ConFig
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs