OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 51
2.4.3.7 SYSTEM CONFIGURATION – RELAY LLP (LS300 Line Leak Panel)
Config
Header Header – General System Settings
tank Tank – Tank Channel specific including geometry and SetPoints
Probe Probe – Level Gauging Probe settings
ReLy tank Relay Tank – Relay Assignments to Tank Channel Specific conditions
ReLy cc Relay CC – Relay Assignments to individual Non-Hazardous CC Inputs
ReLy Sens Relay Sensor – Relay Assignments to individual Leak/Point Level Sensor Inputs
ReLy LLP Relay LLP – Relay Assignments to external LS300 Line Leak failures
ReLy Site Relay Site – Relay Assignments to Site-Specific conditions
ReLy Mode Relay Mode – Relay-specific behavior settings
cc input Non-Hazardous Contact Closure (CC) Inputs
Sensr inp Leak/Point Level Sensor Inputs
Inventory Shift Inventory Report Schedule
tHeft Theft – Detection (Hours of operation)
Modem Modem/Serial C Communications
diaL out Auto-Dial out - Setup for selected Alarms or Tank information
tank LEAk In-Tank Leak Test – Setup
AnaLogout Analog Outputs
ReLy LLP Relay – LS300 Line Leak Test Failure Triggers: Each failed line leak test reported by the external
LS300 Line Leak Panel (LLP) can affect up to three relay outputs. The TMS3000 currently supports
up to 32 Relay Outputs and the TMS2000 systems currently support up to 18 Relay Outputs. The
Group ID shown corresponds to the hardware channel for the LS300 Line Leak Panel.
faiL 0.1 LS300 Line Leak Test Failure Trigger: Any of the three possible LS300 Leak Rates can have
faiL 0.2 its failure affect up to three relays. The LS300 supports Leak Rates of 3.0 GPH, 0.2 GPH,
FaiL 3.0 and 0.1 GPH [12.0 LPH, 0.8 LPH, 0.4 LPH].
Entry Type: numeric list
Range Limits: Each Relay: No (No Relay Assignment), 1-32 (TMS3000), 1-18 (TMS2000)
Note: Each assignment separated by decimal point.
Default/Initialized value: no.no.no
Return Return: Press EDIT (TEST) to exit Relay LLP submenu.
Note: Press STEP (MODE) to return to top of Relay LLP submenu showing faiL 0.1
(Fail 0.1 GPH)