OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 29
2.4.2 IN-TANK LEAK TEST SCHEDULING
ACCESS
Log
Leak test
Config
Clock
Init data
Return
LEAk test In-Tank Leak Test Scheduling: Provides access to setting the duration of the In-Tank Leak Test as
well as the scheduling of Timed Tests. The TMS must have the In-Tank Leak Test parameters
configured prior to addressing the settings in this menu to ensure a complete and accurate system
configuration in support of the required In-Tank Leak Tests. Review and configure these settings in
the Tank Leak submenu of the Configuration menu. The available In-Tank Leak Test scheduling
options apply to each Test Type as shown on the Table below
Manual
Time
Auto
Relay
Test Length
X
X
X
X
Start Time
X
X
Schedule Type
X
X
Schedule Rate
X
X
Schedule Day
X
X
X
Control
X
X
X
test Len Test Length: Choose a Test Length that is appropriate to the tank size, Leak Rate, and local
regulations. Current third-party certifications support the following EPA Approved In-Tank Leak
Test Lengths:
2 hour, 0.2 GPH [0.8 LPH] Test for USTs up to 20,000 Gallons [75,700 Liters] with a
Minimum Percent of used volume of 20%
8 hour, 0.1 GPH [0.8 LPH] Test for USTs up to 20,000 Gallons [75,700 Liters] with a
Minimum Percent of used volume of 20%
8 hour, 0.2 GPH [0.8 LPH] Test for USTs up to 75,000 Gallons [283,900 Liters] with a
Minimum Percent of used volume of 50%
Refer to the National WorkGroup website, www.nwglde.org, or contact Pneumercator for up to
date information.
Entry Type: select list
Range Limits: N/A
Default/Initialized value: 8 hr
Starttime Start Time: This entry allows the user to select an appropriate starting time to begin the in-tank
leak test. Applies to configured Test Type of Timed and Timed-Relay and is used in conjunction
with Schedule Type, Schedule Rate, and Schedule Day to define the complete schedule.
Examples of how these settings interact are provided at the end of this section
Entry Type: 4 digit numeric hours, minutes
Range Limits: 00’00 23’59. (24-hour clock format)
Default/Initialized value: 00’00
Example 12’00 = 12 Noon 23’59 = 11:59 PM 00’00 = Midnight
Schd type Schedule Type: Applies to configured Test Type of Timed and Timed-Relay and is used in
conjunction with Start Time, Schedule Rate, and Schedule Day to define the complete schedule.
Examples of how these settings interact are provided at the end of this section
Entry Type: select list
Range Limits: N/A
Default/Initialized value: this