OPERATION & MAINTENANCE MANUAL TMS2000/3000
TMS Operations and Maintenance Manual.docx February 12, 2018
PAGE 79
ES825-100F/ES825-300FL
(non-discriminating)
Remove and inspect the sensor for physical damage.
Test the sensor by placing in a nonreflective water-filled
container shielded from ambient light. Verify the alarm
received on the system display is as expected. Clean
sensor to remove any contaminants.
ES825-200F/ES825-400FL
(discriminating)
Remove and inspect the sensor for physical damage.
Test the sensor by placing in a nonreflective water-filled
container shielded from ambient light. Verify the alarm
received on the system display is as expected. Repeat
using a container filled with product. Clean sensor to
remove any contaminants.
Float switch sensors: Includes:
LS600, LS600LD, LS610, RSU800
Remove and inspect the sensor for physical damage or
debris that may obstruct the movement of the float. Test
the sensor by manipulating the float. Verify the alarm
received on the system display is as expected. Clean
sensor to remove any contaminants, as necessary.
1. Flip the bottom cap upside-down to confirm the operation
of the float switch
2. Refer to the documentation supplied with the sensor for
proper testing procedures for the hydrocarbon sensing
polymer strip. Contact Pneumercator for additional
information.
Refer to the documentation supplied with the sensor for
proper testing procedures. Contact Pneumercator for
additional information.
Remote Alarms: Includes all RA
and select LC1000 systems
Press the Test button associated with the remote alarm.
It is also recommended to simulate an alarm on the
controlling system to verify the operation of the remote
alarm.
Remote Displays: Includes
TD1000 and ETD1000
Confirm the display of the TMS matches what is displayed
on the Remote Display. Press the Test button to confirm
proper operation of the display and integrated horn.