Time program heating circuit 4 / DHW Prog. no. Level Standard value
3rd Time ON 565 Eu --:-- (h/min)
3rd Time OFF 566 Eu --:-- (h/min)
Copy? 575 Eu No
Default values
No | Yes
576 Eu No
Time program heating circuit 5 Prog. no. Level Standard value
Select Mon-Sun
Mon-Sun | Mon-Fri | Sat-Sun | Mon | Tue | Wed | Thu | Fri | Sat | Sun
600 Eu Mon
1st Time ON 601 Eu 06:00 (h/min)
1st Time OFF 602 Eu 22:00 (h/min)
2nd Time ON 603 Eu --:-- (h/min)
2nd Time OFF 604 Eu --:-- (h/min)
3rd Time ON 605 Eu --:-- (h/min)
3rd Time OFF 606 Eu --:-- (h/min)
Copy? 615 Eu No
Default values
No | Yes
616 Eu No
Holidays heating circuit 1
Prog. no.
2
(1)
Prog. no.
3
(1)
Prog. no.
Level Standard value
Select
Period 1 | Period 2 | Period 3 | Period 4 | Period 5 |
Period 6 | Period 7 | Period 8
641 651 661 Eu Period 1
Start 642 652 662 Eu —.— (day.month)
End 643 653 663 Eu —.— (day.month)
Operating level
Off | Reduced
648 658 668 Eu Off
(1) Parameters only visible if heating circuit is installed!
Heating circuit 1
Prog. no.
2
(1)
Prog. no.
3
(1)
Prog. no.
Level Standard value
Comfort setpoint 710 1010 1310 Eu 20.0 °C
Reduced temp setpoint 712 1012 1312 Eu 18 °C
Frost protection setpoint 714 1014 1314 Eu 10.0 °C
Heating curve slope 720 1020 1320 Eu 1.24
Heating curve displacement 721 1021 1321 E 2.0 °C
Heating curve adaption
Off | On
726 1026 1326 E Off
Summer/winter heating limit 730 1030 1330 Eu 18°C
24-hour heating limit 732 1032 1332 E 0 °C
Flow temp setpoint min 740 1040 1340 E 8 °C
Flow temp setpoint max 741 1041 1341 E 80 °C
Flow temp setpoint room stat 742 1042 1342 E - - - °C
Swi-on ratio room stat 744 1044 1344 E - - - %
Delay heat request 746 1046 1346 E 0 s
Room influence 750 1050 1350 C - - - %
Room temp limitation 760 1060 1360 E 0.5 °C
Central heating boost 770 1070 1370 E - - - °C
9 Settings
7658013 - 02 - 15092016 Paramount four 30 – 115 kW 59