Heating circuit 1
Prog. no.
2
(1)
Prog. no.
3
(1)
Prog. no.
Level Standard value
Quick setback
Off | Down to reduced setpoint | Down to frost prot
setpoint
780 1080 1380 E Down to reduced
setpoint
Optimum start control max 790 1090 1390 E 0 min
Optimum stop control max 791 1091 1391 E 0 min
Reduced setp increase start 800 1100 1400 E - - - °C
Reduced setp increase end 801 1101 1401 E -15 °C
Continuous pump operation
No | Yes
809 1109 1409 E No
Overtemp protect pump circ
Off | On
820 1120 1420 E Off
Mixing valve boost 830 1130 1430 E 5 °C
Actuator running time 834 1134 1434 E 140 s
Floor curing function
Off | Functional heating | Curing heating | Curing/
functional heating | Functional/curing heating |
Manually
850 1150 1450 E Off
Floor curing setp manually 851 1151 1451 E 25 °C
Floor curing setp current 855 1155 1455 E - - - °C
Floor curing day current 856 1156 1456 E - - -
Excess heat draw
Off | Heating mode | Always
861 1161 1461 E Heating mode
With buffer
No | Yes
870 1170 1470 E Yes
With prim contr/system pump
No | Yes
872 1172 1472 E Yes
Pump speed reduction
Operating level | Characteristic | Temp differential
nominal
880 1180 1480 E Characteristic
Pump speed min 882 1182 1482 C Paramount four 30:
35%; Paramount four
40: 35 %;
Paramount four 50–
115: 30 %
Pump speed max 883 1183 1483 C Paramount four 30:
63%; Paramount four
40: 80%
Paramount four 50–
115: 80%
Curve readj at 50% speed 888 1188 1488 E 10 %
Flow setp readj speed ctrl
No | Yes
890 1190 1490 E YesNo
Operating level changeover
Off | Reduced | On
898 1198 1498 E Reduced
Optg mode changeover
None | Off | Reduced | On | Timed
900 1200 1500 E Off
(1) Parameters only visible if heating circuit is installed!
DHW Prog. no. Level Standard value
Hot water temp setpoint 1610 Eu 55 °C
Reduced temp setpoint 1612 E 45 °C
Hot water temp setpoint max 1614 E 65 °C
9 Settings
60 Paramount four 30 – 115 kW 7658013 - 02 - 15092016