DHW Prog. no. Level Standard value
Release
24h/day | Time setting central heating | Time hot water
1620 Eu Time hot water
Charging priority
Absolute | Shifting | None | MC shifting, PC absolute
1630 E MC shifting, PC
absolute
Legionella function
Off | Periodically | Fixed weekday
1640 E Fixed weekday
Legionella funct periodically 1641 E 7
Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday | Saturday | Sunday
1642 E Sunday
Legionella funct time 1644 E - - -
Legionella funct setpoint 1645 E 65 °C
Legionella funct duration 1646 E - - - min
Legionella funct circ pump
Off | On
1647 E On
Circulating pump release
Time setting 3/CHP | Hot water release | Time hot water | Time auxiliary
1660 C Hot water release
Circulating pump cycling
Off | On
1661 C On
Circulation setpoint 1663 E 55 °C
Optg mode changeover
None | Off | On
1680 E Off
Consumer circuit / swimming pool circuit Consumer
circuit 1
Prog. no.
Consumer
circuit 2
Prog. no.
Swimming
pool circuit
Prog. no.
Level Standard value
Flow temp setp cons request 1859 1909 1959 C 70 °C
Hot water charging priority
No | Yes
1874 1924 1974 E Yes
Excess heat draw
Off | On
1875 1925 1975 E On
With buffer
No | Yes
1878 1928 1978 E Yes
With prim contr/system pump
No | Yes
1880 1930 1980 E Yes
Swimming pool Prog. no. Level Standard value
Setpoint solar heating 2055 Eu 26°C
Setpoint source heating 2056 Eu 22°C
Charging priority solar
Priority 1 | Priority 2 | Priority 3
2065 E Priority 3
Swimming pool temp max 2070 E 32 °C
With solar integration
No | Yes
2080 E Yes
Primary control/feed pump Prog. no. Level Standard value
Flow temp setpoint min 2110 E 8 °C
Flow temp setpoint max 2111 E 80 °C
Syst pump on heat gen lock
Off | On
2121 E Off
Mixing valve boost 2130 E 0 °C
Actuator running time 2134 E 140 s
9 Settings
7658013 - 02 - 15092016 Paramount four 30 – 115 kW 61