Primary control/feed pump Prog. no. Level Standard value
Primary contr/system pump
Before buffer | After buffer
2150 E After buffer
Boiler Prog. no. Level Standard value
Release below outside temp 2203 E - - - °C
Full charging buffer
Off | On
2208 E Off
Setpoint min 2210 E 20 °C
Setpoint max 2212 E 85 °C
Setpoint manual control 2214 Eu 60 °C
Burner running time min 2241 E 1 min
Burner off time min 2243 E 7 min
SD burner off time 2245 E 20 °C
Pump overrun time 2250 E 2 min
Pump overr time after HW 2253 E 1 min
Syst frost prot boiler pump
Off | On
2300 E On
Boiler pump on heat gen lock
Off | On
2301 E Off
Impact heat generation lock
Heating mode only | Heating and HW mode
2305 E Heating mode only
Temp differential max 2316 C - - -
Temp differential nominal 2317 C 15 °C
Pump modulation
None | Demand | Boiler setpoint | Temp differential nominal | Burner output
2320 E Demand
Pump speed min 2322 E 10 %
Pump speed max 2323 E 100 %
Output nominal 2330 E Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60 : 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Output basic stage 2331 E Paramount four 30: 6
kW; Paramount four
40: 9 kW
Paramount four 50:
10 kW; Paramount
four 60: 12 kW; Para‐
mount four 80: 21 kW;
Paramount four 95:
20 kW; Paramount
four 115: 25 kW
Output at pump speed min 2334 E 25 %
Output at pump speed max 2335 E 100 %
9 Settings
62 Paramount four 30 – 115 kW 7658013 - 02 - 15092016