Boiler Prog. no. Level Standard value
Fan output heating max
(1)
2441 E Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Fan output full charging max
(1)
2442 E Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Fan output DHW max
(1)
2444 E Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
Controller delay
Off | Heating mode only | Hot water mode only | Heating and HW mode
2450 E Heating mode only
Controller delay fan output
(1)
2452 E Paramount four 30:
10,0 kW; Paramount
four 40: 14.0 kW
Paramount four 50:
20,0 kW; Paramount
four 60: 22,5 kW; Pa‐
ramount four 80: 34,5
kW; Paramount four
95: 36,0 kW; Para‐
mount four 115: 40.0
kW
Controller delay duration 2453 E 40 s
Switching diff on CHs 2454 E 4 °C
Switching diff off min CHs 2455 E 5 °C
Switching diff off max CHs 2456 E 10 °C
Switching diff on HW 2460 E 5 °C
Switching diff off min HW 2461 E 6 °C
Switching diff off max HW 2462 E 8 °C
Delay heat req special op 2470 E 0 s
Pressure switch shutdown
Start prevention | Lockout position
2500 E Start prevention
Gas energy metering
Off | On
2550 C Off
Gas energy metering correction 2551 C 1.0
(1) The kW settings are approximate values. Exact values can be determined by the gas meter for example.
9 Settings
7658013 - 02 - 15092016 Paramount four 30 – 115 kW 63