Chapter 5 Function parameter
45
between deceleration time 1
and deceleration time 2
Forward/reverse rotation
deadband
Set frequency lower than
lower limit
frequency
mode
0:
running at lower limit frequency
1: stop
2: zero speed running
Setting
cumulative
power-on
arrival time
Setting cumulative running
arrival time
Start protection selection
Frequency detection value
(FDT1)
0.00Hz to F0.19(maximum
frequency)
Frequency detection
hysteresis value (FDT1)
0.0% to 100.0% (FDT1 level)
Frequency reaches
detection width
0.00 to 100% (maximum
frequency)
Frequency detection value
(FDT2)
0.00Hz to F0.19 (maximum
frequency)
Frequency detection
hysteresis value (FDT2)
0.0% to 100.0% (FDT2 level)
Random arrivals frequency
detection value 1
0.00Hz to F0.19 (maximum
frequency)
Random arrivals frequency
detection width 1
0.00% to 100.0% (maximum
frequency)
Random arrivals frequency
detection value 2
0.00Hz to F0.19 (maximum
frequency)
Random arrivals frequency
detection width 2
0.00% to 100.0% (maximum
frequency)
Zero current detection level
0.0% to 300.0% (rated motor
current)
Zero current detection
delay time
Overrun value of output
current
0.0% (not detected)
0.1% to 300.0% (rated motor
current)
Output current overrun
detection delay time
Random arrivals current 1
0.0% to 300.0% (rated motor
current)
Random arrivals current 1
width
0.0% to 300.0% (rated motor
current)