Chapter 5 Function parameter
48
Ten thousands digit: Communication
abnormal(
Err.16
)(same as units digit)
Fault protection action
selection 2
Units digit: Encoder fault(Err.20)
0: Free stop
1:Switch to V/F and then stop at the
selected mode
2:Switch to V/F and continue to run
Tens digit: function code read and
write abnormal (Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor overheating
(Err.45) ( same as F8.17 units digit)
Ten thousands digit: Running time
arrival(Err.26)(same as F8.
17 units
digit)
Fault protection action
selection 3
Units digit:User-defined fault
1(Err.27) (same as F8.17 units digit)
Tens digit:User-defined fault 2(Err.28)
(same as F8.17 units digit)
Hundreds digit: Power-on time arrival
(Err.29) ( same as F8.17 units digit)
Thousands digit: Reserved
Ten thousands digit: PID feedback
loss when running (Err.31) (same as
F8.17 units digit)
Fault protection action
selection 4
Units digit: Too large speed deviation
(Err.42) ( same as F8.17 units digit)
Tens digit: Motor over-speed (Err.43)
Hundreds digit: Initial position error
(Err.51)
( same as F8.17 units digit) Thousands
digit: Reserved Ten thousands digit:
Reserved
0: current frequency running
1: setting frequency running
2: upper frequency running
3: down frequency running
4: Abnormal reserve frequency
running
Abnormal reserve
frequency
Momentary power cut
action selection
0: Invalid
1: Deceleration
2: Deceleration and stop
Recovery voltage
judgment time of