PR4000 9mt 4x1000W METAL HALIDE
50
TL073-11-02-03
01-02-2011
CAUSE
The “DAS” TP0401 protection panel is defective.
REMEDY
Replace the panel.
FAULT
The machine stops with the high water temperature signal lamp ignited.
CAUSE
The level of the coolant in the radiator is low.
REMEDY
Verify the level and add coolant if necessary.
CAUSE
Radiator net or radiator fin clogged with dust.
REMEDY
Clean net or fin carefully.
CAUSE
Radiator fan does not work.
REMEDY
Check the fan.
CAUSE
The protection panel “DAS” TP0401 is defective.
REMEDY
Replace the panel.
FAULT
The machine stops with the battery charge signal lamp ignited.
CAUSE
The battery is defective.
REMEDY
Replace the battery.