PR4000 9mt 4x1000W METAL HALIDE
TL073-11-02-03
01-02-2011
CAUSE
The engine’s alternator is failure.
REMEDY
Check it and eventually contact a Kubota assistance centre.
CAUSE
The protection panel “DAS” TP0401 is defective.
REMEDY
Replace the panel.
FAULT
• After refueling, the fuel level monitor does not move.
CAUSE
The fuel level monitor does not work.
REMEDY
Check the fuel level monitor and its relative electrical connection.
CAUSE
The floating does not work.
REMEDY
Check the floating and its relative electrical connection. If the sensor is blocked, eventually replace
it.
FAULT
• With the engine in motion the hour meter does not work.
CAUSE
The hour meter does not work.
REMEDY
Check the hour meter and its relatives electrical connection.