N93-572-88 Issue 12 NH Page 24 of 52 © Protec Fire Detection plc 2020
7.5 Loop Device Sensitivity Programming
This setting is only applicable to automatic detectors and allows two detection sensitivities to be
programmed. The 6100 offers a range of sensitivities that can be used to tailor the response of the
detector to suit individual site conditions. The 6100 supports the following sensitivities.
Table 7.0 Automatic Detector Sensitivity Setting Options
Programmed
Sensitivity
Typical Applications
NONE
Used for non-detector types ( interfaces, MCP’s etc )
OFFICE
For use in general environments ( offices, for example )
BEDROOM
Incorporates an anti-steam algorithm for use in bedrooms
ENHANCED
Enhanced sensitivity for use in clean room environments
NO OP
Turns optical-heat devices into heat only devices
Note: The spacing distance for heat detectors must be adopted for the
loop device if this sensitivity is used
PRISON
Prison Cells
7.6 Loop Sounder Volume Programming
Individual loop sounder devices can have their volume level programmed. Volume settings of high,
medium and low are supported ( please consult the datasheet for the individual loop sounder product
to ensure it can support programmable volume ).