page 53
Industrial Power Corruptor Manual Rev 1.00
Trip:src L1-L2 V
Trip:src L2-L3 V
Trip:src L3-L1 V
The IPC tripped its main circuit breaker because the voltage between the indicated pair of terminals, on the source side,
exceeded 125% of the IPC’s voltage rating.
Trip:Stuck0 RLNN
The IPC tripped its main circuit breaker because the one of its internal relays, indicated by NN, failed to transition from
its “off” state to its “on” state in the time allowed by the IPC. The relay may be defective, or it may need mechanical re-
alignment. Service is required. Contact the factory.
Trip:Stuck1 RLNN
The IPC tripped its main circuit breaker because the one of its internal relays, indicated by NN, failed to transition from
its “on” state to its “off” state in the time allowed by the IPC. The relay may be defective, or it may need mechanical re-
alignment. Service is required. Contact the factory.
Turn Brker on.
If it is safe to do so, turn the main circuit breaker on. It is located on the back of the IPC, in the center.
Turning Brkr on.
This message only occurs if your IPC has the motor-operated circuit breaker option. It shows that the motor is in the
process of turning on the main circuit breaker, on the back of the IPC.
Waiting for PC.
The IPC is ready to begin communication with a Windows PC running the IPC software package. (Under certain
circumstances – after a lengthy communication interruption — this message may appear even when the IPC and the PC
are communicating. Press the “disconnect” button on the IPC software package, then reconnect.)
Xfrm NNNC ovrtemp
The IPC’s internal transformer is NNN degrees C over its programmed temperature limit, probably due to a rapid
sequence of lengthy, high current sags or swells. Allow it to cool. It will automatically clear this error message when it
is no longer over its temperature limit.
B - Software error messages
“Your computer is running too slow for once-per-second power readings. The readings will be updated as rapidly as
possible.”
Most recent event terminated due to no setup”
MostRecentEventOutcomeStrings(2) = “Most recent event terminated due to panic”
MostRecentEventOutcomeStrings(3) = “Most recent event terminated due to blown snubber fuse”
MostRecentEventOutcomeStrings(4) = “Most recent event terminated due to IGBT fault”
MostRecentEventOutcomeStrings(5) = “Most recent event terminated due to overheating relay”
MostRecentEventOutcomeStrings(6) = “Most recent event terminated because event was canceled”
MostRecentEventOutcomeStrings(7) = “Most recent event terminated because no zero crossing was found”
Command N was rejected by processor N