PULSAR MEASUREMENT
121
The third parameter for each relay determines the pump group. You can
have two groups of pumps, and all similar duties within that group will
operate together.
P212, 222, 232 Relay Pump Group
By default, all pump groups are set to 1, but if you want to have another
group, then set this parameter to 2, for each pump relay that should operate
together as part of a second group.
The fourth parameter and the fifth parameter for each relay set the pump
ON” and “OFF” points, which are entered in Measurement units P104. For
pump down the “ON” is set higher than OFF”. For pump up then “ON” is
set lower than OFF”. See the appropriate pump duty, function table
(P212, 222, 232) for further information.
P213, 223, 233 Relay Setpoint 1
This parameter determines the ‘ON’ point of the pump.
P214, 224, 234 Relay Setpoint 2
This parameter determines the ‘OFF’ point of the pump.
The sixth parameter will determine the service ratio that will be used to
switch the pump, when pump duty selected is a Service Ratio duty.
P210, 220, 230 = 6, 7 or 9 (Service ratio)
P215, 225, 235 Relay Setpoint 3
This parameter determines the Service Ratio in values of %. See the
appropriate pump duty function, table (P211, 221, 231), for further
information.
P219, 229, 239 Relay Max Rate
This parameter will allow a pump to be switched at a pre-determined Rate
of change of Level, irrespective of the “ON” level setpoint P213, 223, 233.
Once a pump relay has been switched “ON” by the pre-determined Rate of
Change, it will remain energised until the level reaches the “OFF” level
setpoint P214, 224, 234.
Max. Rate is entered in Measurement Units (P104) per minute and can be
entered as either positive (increasing level) or negative (decreasing level)
values.