PULSAR MEASUREMENT
51
Alarm relays, via the Quick Setup menu are entered as a % of span and are
as follows:
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Control Down
One
Control 1
80%
20%
Control Down
Two
Control 1
Control 2
80%
70%
20%
20%
Control Down
Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Control Up
One
Control 1
20%
20%
Control Up
Two
Control 1
Control 2
20%
30%
20%
20%
Control Up
Three
Control 1
Control 2
Control 3
20%
30%
40%
20%
20%
20%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%