The default values used for determining the relay setpoints, when setting
Alarms and Pump relays, via the Quick Setup menu are entered as a % of
span and are as follows.
APPLICATION
NO. OF
PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1
Pump 2
50%
70%
20%
20%
Pump Down
Three
Pump 1
Pump 2
Pump 3
50%
60%
70%
20%
20%
20%
APPLICATION
NO. OF
PUMPS
PUMP NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Up
One
Pump 1
50%
80%
Pump Up
Two
Pump 1
Pump 2
50%
30%
80%
80%
Pump Up
Three
Pump 1
Pump 2
Pump 3
50%
40%
30%
80%
80%
80%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%