PULSAR MEASUREMENT
73
Wait….
Type of transducer being used
Units of flow as on display and used for
calculations.
1 = Litres 2 = Cubic metres
3 = Cubic Feet 4 = UK gallons
5 = US gallons 6 = Mil. USG
Units of time that volume units will be
displayed and calculated in
Used to enter dimensions and displayed
where appropriate
1 = Metres 2 = Centimetres
3 = Millimetres 4 = Feet
5 = Inches
Distance from the end of the transducer
horn (dB Mach3) or face of the
transducer to the material at the
bottom of the measuring element
Distance from empty point (P105) to
zero flow.
Distance from zero flow to max flow. It
should be noted that any change to
P704 updates P106 Span and vice versa.
Enables the flow totaliser, P820, options
are 0=Off, 1=On. Note this totaliser can
be viewed during run via the totaliser
“Hot Key” It can be reset but only via
P820, whilst in “program mode”.
Enables the totaliser to be displayed in
the auxiliary display whilst in “run
mode”. Note the totaliser is “resettable”
whilst in run mode via the totaliser hot
key.