Enforcer: Programming Manual 
Page: 13 
Change Output Programming  
1.  Press or to scroll to 'CHANGE OUTPUTS'. Press . 
2.  'Endstation Outputs' will be displayed. Press to program 
any endstation outputs (on the I/O module if connected), or 
press  for the next function. Use [ or ] to scroll through 
the outputs or the select the shortcut number. 
3.  'ZEM Outputs' will be displayed. Press to program any ZEM 
outputs (on the EURO-ZEM8+ or EURO-ZEM8+PSU if 
connected), or press  for the next function.  
4.  'Wireless Bells'' will be displayed. Press to program any 
wireless output types or press  for the next function.  
5.  'Output Module Outputs'' will be displayed. Press to 
address an output module (EURO-OEM8R8T or EURO-
OEM16R+PSU if connected) or press  for the next function.  
6.  'Keypad Outputs' will be displayed. Press to program any 
outputs on any additional keypads connected or press  for 
the next function.  
7.  'Reader Outputs' will be displayed. Press to program any 
outputs on any readers connected or press  to return to the 
Engineer menu for the next function.  
8.  'User Outputs' will be displayed. User Outputs can be activcated 
from the Master Manager Menu, and can also be programmed 
to be operated via a keyfob. If required, in the ‘Program Keyfob 
Buttons’ in the menu ‘WIRELESS DEVICE CONTROL’ menu and 
program the outputs for types 170-199. 
 
 
 
 
 
 
 
3.7 Assign Keypads/Readers 
Any additional keypads or readers must be addressed correctly before enabling them in this function. 
The Enforcer keypad is automatically addressed as 0 on initial power up. Refer to installation manual 
for more information. 
Address 
Up to 3 x additional wired keypads or readers may be installed. 4 x wireless arming stations can 
also be installed. Address 0 is used for the Enforcer on-board keypad. 
NOTE: Each keypad has its own individual menu that programs the key-click volume, tag volume 
and master volume. It will address a keypad, show the status of the keypad inputs (if 
programmed), force the backlight on or off and the identification number of a tag (once a tag is 
presented). The PA/Fire timer can be programmed. This menu also addresses the keypad. 
To enter the keypad menu, press and hold the  key until ‘SECURITY CODE’ is displayed, and 
then enter ‘2000’. This function is also used to address the keypad. 
NOTE 2: Wireless arming stations (LEDRKP-WE) are learnt to one the 4 wireless arming station 
allocations on the Enforcer. However, are seen as addresses 4-7 in ‘Assign Keypads and Readers’ 
Type 
[0] Keypad. [1] Reader. [2] Not Used. 
Reader is 
If a reader is installed, the following options can be assigned to the reader: 
[0] Set Point: Reader used for setting and unsetting.  
[1] Not Used: Reader disabled 
[2] Access Control: If an access control system is installed then the reader must be 
programmed as this type. The lock open time and door open time can be programmed (in 
seconds). 
[3] Unset Only: If the Reader is to be used as an unset device only, select this type. 
[4] Entry Control: Used to lock/unlock doors. The external or internal reader can have 
magnetic locks connected to them. This option is used in conjunction with ‘tag opens doors’ in 
'SITE OPTIONS' page: 18. The lock open time and door open time can be programmed (in 
seconds). 
 
CHANGE OUTPUTS?
Endstation
Outputs?
BELL O/P  [0014]
Siren Any
ZEM Outputs?
Wireless Bells?
Output Module
Outputs?
User Outputs?