EasyManua.ls Logo

Pyronix Matrix 832

Pyronix Matrix 832
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Matrix 424/832/832+ LCD Programming Manual
RINS916-6 Page 47
15.7 Allocating Telephone Numbers to Alarm Types (Function 706)
Press .
This starts the function
ENTER PARTITION
_
Enter 1 digit for the partition (1 – 4).
Example shows Partition
1
This display is quickly
followed by the next
ENTER PARTITION
_1
Enter the alarm type (1 – 8)
Valid alarm types are:
1 = Alarm
2 = PA
3 = Fire
4 = Maintenance
5 = Open/Close
6 = Medical Alarm
7 = Confirmed
8 = Omit
This display is quickly
followed by the next
ENTER ALARM TYPE
_
ENTER ALARM TYPE
_6
Enter 1 digit to select the telephone number to
be used for Tel 1 (1 – 9).
NOTE: A leading zero is always shown.
Press to accept.
Example shows
telephone number 1
ENTER TEL ALLOC
01
Enter 1 digit to select the telephone number to
be used for Tel 2 (1 – 9).
NOTE: A leading zero is always shown.
Press to accept.
Example shows
telephone number 2
ENTER TEL ALLOC
02
Enter 1 digit to select the telephone number to
be used for Tel 3 (1 – 9).
NOTE: A leading zero is always shown.
Press to accept.
Example shows
telephone number 3
ENTER TEL ALLOC
03
Enter 1 digit to select Tel 1 & Tel 2 reporting
sequence (1 – 3).
Valid sequences are:
1 = Only send to Tel 1
2 = Send to Tel 1 & Tel 2
3 = Tel 2 only if Tel 1
busy
ENTER SEQUENCE
02
Press to accept the changes.
NOTE: Default is Telephone Number 1 for telephone 1, Telephone Number 2 for telephone 2,
and 0 for telephone 3, for all alarm types.

Table of Contents

Other manuals for Pyronix Matrix 832

Related product manuals