20
|
nVent.com/RAYCHEM RAYCHEM-OM-EU2032-NGCUIT3EX-EN-2203
The minimum configuration to use the NGC-30 software is:
• NGC-UIT3 hardware
• At least one of the following:
- NGC-30-CRM/-CRMS
- RMM2 Remote Monitoring Module
- RMC Module
- Elexant 5010i and/or NGC-20 Controller
Maximum optional equipment configuration:
• Up to 52 Heat Trace Controller Boards (total count in any combination)
- NGC-30-CRM
- NGC-30-CRMS
• Up to 16 RMM2 modules (8 channel RTD multiplexing hubs)
• Up to 4 PLI modules (127 RTDs if SES/SPC transmitters are used, or 255 RTDs if 700-TT transmitters are used)
• Up to 247 Elexant 5010i / NGC-20 controllers
• Up to 247 RMM-DI modules
Total combination of output devices including NGC-30-CRM/-CRMS, NGC-20 and RMC DO cannot exceed 260 circuits.
The software is designed to run only on the NGC-UIT3 hardware platform. Prior to shipment, the software is installed into a
nonvolatile area of the NGC-UIT3 memory. During the initial power-up, you will see a blue background “splash” window for
approximately 30 seconds as the system software is loaded and initializes.