This window enables or disables the various load shed zones. The actual configuration and implementation of these zones are done
in Supervisor.
Fig. 3.20 Setup | Load Shed window
Each independent controller can be assigned to none, some or all of the 16 independent zones. Those zones that have been assigned
to the controller requires the Enable box to be checked for the Load Shedding process to activate.
If the Failsafe box is checked, the controller will revert to the failsafe mode configured in the Setup|Circuit window if the NGC-20
controller loses communication with Supervisor.

The status Circuit window displays the status information for individual Circuits. Data in the status menus cannot be changed; it is
informational only.
Fig. 3.21 Status | Circuit window