Maintenance
54
English Reflexomat with Touch controller06.07.2016 - Rev. B
10
Maintenance
CAUTION
Risk of burns
Escaping hot medium can cause burns.
Maintain a sufficient distance from the escaping medium.
Wear suitable personal protective equipment (safety gloves and goggles).
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
Ensure that the system is voltage-free before installing the device.
Ensure that the system is secured and cannot be reactivated by other persons.
Ensure that installation work for the electric connection of the device is carried out by an electrician, and in compliance with
electrical engineering regulations.
The device is to be maintained annually.
The maintenance intervals depend on the operating conditions and the degassing times.
The annual maintenance is displayed upon expiry of the set operating time. Use "OK" to acknowledge the "Maintenance recommended"
message. Reset the maintenance counter in the Customer menu.
Note!
The maintenance intervals for the secondary tanks may be extended to 5 years if operation has been trouble
-free.
Note!
Maintenance work
must be carried out and confirmed by specialist personnel or the Reflex Customer Service, see
chapter
10.4 "Maintenance certificate " on page 59 .
10.1
Maintenance schedule
The maintenance schedule is a summary of maintenance tasks to be carried out regularly.
Maintenance task
Conditions
Interval
= Ch eck, = Servi ce, = Clean
Check for leaks.
"CO" compressor.
Screw connections of the compressed air connections.
Annually
Check switching points.
"CO" compressor cut-in pressure.
Insufficient water.
Make-up with water.
Annually
Clean "ST" dirt trap.
see chapter 10.3.2 "Cleaning the dirt trap" on page 58 .
Depending on the operating
conditions
Remove condensate from the primary tank and the secondary tanks, if
applicable.
see chapter 10.3.1 "Cleaning the tanks" on page 57 .
Annually

Table of Contents