Operation
Reflexomat with Touch controller06.07.2016 - Rev. B English
8
Operation
8.1
Operating modes
8.1.1
Automatic mode
After successful commissioning, start the Automatic mode from the device. The Automatic mode is suitable for continuous device
operation and the controller monitors the following functions:
Maintain pressure
Compensate expansion volume
Automatic make-up
1
. Press "AUTO“.
The "CO" compressor and the "PV1" solenoid valve are
regulated by the controller so that the pressure remains
constant at a regulation range of ± 0.1 bar.
Faults are displayed and evaluated.
Reflexomat RS../1
800l
25%
1.4 bar
System
0l
NSP
0l