— English Reflexomat with Touch controller — 06.07.2016 - Rev. B
Damage due to improper installation
Additional device stresses may arise due to the connection of pipes or system equipment.
• Ensure that pipes are connected from the device to the system without stresses being induced.
• If necessary, provide support structures for the pipes or equipment.
Comply with the following notes regarding the installation of
the primary tank and the secondary tanks:
All flange openings at the tanks are viewing and
maintenance openings.
– Place the tanks with sufficient distances to sides and
ceiling.
Install the tanks on a level surface.
Ensure rectangular and free-standing position of the tanks.
Use only tanks of the same type and dimensions when
using secondary tanks.
Ensure proper functioning of the "LIS" level sensor.
Property damage caused by overpressure. Do
not attach the tanks firmly to the floor.
Install the control unit on the same level as the tanks.