Controller
46
— English Reflexomat with Touch controller — 06.07.2016 - Rev. B
9.3
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and active operating mode.
9.3.1.1
Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
Note!
For a description of the operation, see chapter
9.1 "Operator panel" on page 44 .
A three-digit PM code is assigned to the setting options.
PM code
Description
001 Select the language
002 Set the time
003 Set the date
Execute null balancing
– The primary tank must be empty!
– The system checks whether the signal from the level sensor matches the selected primary tank.
005 Set the P
0
minimum operating pressure, see chapter 7.2 "Determining the P
0
minimum operating pressure for the
controller" on page 35 .
Make-up >
021 • Make-up ON at … %
022 • Make-up OFF at … %
023 • Maximum make-up time …min
024 • Maximum make-up cycles … /2 h
027 • With contact water meter "Yes/'No"
– If "Yes", continue with 028
028 • Reset make-up quantity "Yes/No"
029 • Maximum make-up quantity ... l
030 • With softening "Yes/'No"
– If "Yes", continue with 031
031 • Block make-up "Yes/No" (if water capacity is exhausted)
033 • Hardness reduction … °dH = GHactual – GHtarget
032 • Soft water capacity
• Fillsoft I: Soft water capacity = 6000 l / hardness reduction
• Fillsoft II: Soft water capacity = 12000 l / hardness reduction
034 • replacement interval… months (for softening cartridges according to manufacturer).
007 Maintenance interval… months
008 Floating contact
• Message selection >
• Message selection: only messages marked with "√“ are output.
• All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
009 • Brightness … %
010 • Screen saver brightness … %
011 • Screen saver delay …min
Information >
• Tank: Tank information
• Software version