— English Reflexomat with Touch controller — 06.07.2016 - Rev. B
Regularly clean the "ST" dirt trap. The cleaning intervals depend on the local operational conditions.
. Switch to Stop mode.
– Press "Stop" on the controller's operator panel.
. Close the ball valves upstream and downstream of the
"ST" (1) dirt trap.
. Slowly unscrew the dirt trap insert (2) from the dirt trap in
order for the residual pressure to escape from the pipeline
segment.
. Pull the mesh from the dirt trap insert and rinse it with clear
water. Use a soft brush for cleaning.
. Re-insert the mesh into the dirt trap insert, check the gasket
for damage, and screw the dirt trap insert back into the
housing of the "ST" (1) dirt trap.
. Re-open the ball valves upstream and downstream of the
"ST" (1) dirt trap.
. Switch to Automatic mode.
– Press "Auto" on the controller's operator panel.
1 "ST" dirt trap 2 Dirt trap insert
Note!
Clean all other installed dirt traps (in the Reflex Fillset, for
example).