C1: Motor and system parameters
Code Name Setting range Default Min. Attri.
C1.00 Motor type
0: Asynchronous motor
1: Synchronous motor (only
for EFC 5610)
0 – Stop
C1.01 Motor parameter tuning
0: Inactive
1: Static auto-tuning
2: Rotational auto-tuning
①
0 – Stop
C1.02 Expert mode
0: Standard mode
1: Expert mode
0 – Stop
C1.05 Motor rated power 0.1...1,000.0 kW DOM 0.1 Stop
C1.06 Motor rated voltage 0...480 V DOM 1 Stop
C1.07 Motor rated current 0.01...655.00 A DOM 0.01 Stop
C1.08 Motor rated frequency 5.00...400.00 Hz 50.00 0.01 Stop
C1.09 Motor rated speed 1...30,000 rpm DOM 1 Stop
C1.10 Motor rated power factor
0.00: Automatically
identified
0.01...0.99: Power factor
setting
0.00 0.01 Stop
C1.11
Motor poles
①
2...256 4 1 Stop
C1.12 Motor rated slip frequency 0.00...20.00 Hz DOM 0.01 Run
C1.13
Motor inertia mantissa
①
1...5,000 DOM 1 Stop
C1.14
Motor inertia exponent
①
0...7 DOM 1 Stop
C1.15 Torque constant 0.01…200 DOM 0.01 Run
C1.20 Motor no-load current 0.00...[C1.07] A DOM 0.01 Stop
C1.21 Stator resistance 0.00...50.00 Ω DOM 0.01 Stop
C1.22 Rotor resistance 0.00...50.00 Ω DOM 0.01 Stop
C1.23 Leakage inductance 0.00...200.00 mH DOM 0.01 Stop
C1.24 Mutual inductance 0.0...3,000.0 mH DOM 0.1 Stop
C1.25 Rotor leakage inductance 0.00...200.00 DOM 0.01 Stop
C1.69
Motor thermal model protection
setting
0: Inactive
1: Active
0 – Stop
C1.70 Motor overload pre-warning level 100.0...250.0 % 100.0 0.1 Run
C1.71 Motor overload pre-warning delay 0.0...20.0 s 2.0 0.1 Run
EFC 3610 / EFC 5610 Bosch Rexroth AG
Start-up
DOK-RCON03-EFC-X610***-QU11-EN-P
43/87