Code Name Setting range Default Min. Attri.
E0.07 Digital setting frequency 0.00...[E0.09] Hz 50.00 0.01 Run
E0.08
Maximum output fre-
quency
50.00...400.00 Hz 50.00 0.01 Stop
E0.09
Output frequency high
limit
[E0.10]...[E0.08] Hz 50.00 0.01 Run
E0.10
Output frequency low
limit
0.00...[E0.09] Hz 0.00 0.01 Run
E0.17 Direction control
0: Forward/Reverse
1: Forward only
2: Reverse only
3: Swap default direction
0 – Stop
E0.25
Acceleration / Decelera-
tion curve mode
0: Linear mode
1: S-curve
0 – Stop
E0.26 Acceleration time 0.1...6,000.0 s DOM 0.1 Run
E0.27 Deceleration time 0.1...6,000.0 s DOM 0.1 Run
E0.35 Start mode
0: Start directly
1: DC-braking before start
2: Start with speed tracing
3: Automatic start / stop ac-
cording to setting frequency
0 – Stop
E0.50 Stop mode
0: Decelerating stop
1: Freewheeling stop 1
2: Freewheeling stop 2
0 – Stop
Tab. 3-5: Start-up parameters
36/91
Start-up
Rexroth Frequency Converter VFC
3610 / VFC 5610
Bosch Rexroth AG R912005518_Edition 16