Code Name Setting range Default Min. Attri.
C0.27
Stall overcurrent
prevention level
③
20.0 %...[C2.42] 150.0 0.1 Stop
C0.28
Phase loss protection
mode
0...3 3 – Run
C0.29
Converter overload
pre-warning level
20.0...200.0 % 110.0 0.1 Stop
C0.30
Converter overload
pre-warning delay
0.0...20.0 s 2.0 0.1 Stop
C0.40
Power loss ride-
through mode
0: Inactive; 1: Output disabled
2: Regain kinetic energy
3: Regain kinetic energy, decel-
erate to stop
0 – Stop
C0.41
Power loss ride-
through recovery delay
0.10...30.00 s 0.50 0.01 Stop
C0.42
Power loss ride-
through action voltage
1P 200 VAC: 216...366 V 240
1 Stop
3P 380 VAC: 406...739 V 440
C0.43
Power loss ride-
through recover voltage
1P 200 VAC: 223...373 V 250
1 Stop
3P 380 VAC: 413...746 V 450
C0.44
Power loss ride-
through deceleration to
stop time
0.1...6,000.0 s 5.0 0.1 Stop
C0.50 Fan control
0: Automatically controlled
1: Always on
2: On when converter run
0 - Run
C0.51 Fan total running time 0...65,535 h 0 1 Read
C0.52 Fan maintenance time 0...65,535 h (0: Inactive) 0 1 Stop
C0.53
Fan total running time
reset
0: Inactive; 1: Active
Resets to '0' after action is
executed
0 – Run
①
: this parameter is only available with models of 5K50 and above.
②
: the parameters are only available with models of 22K0 and below.
③
: percentage of frequency converter rated current.
Setting range of C0.25:
0: Both disabled
1: Stall overvoltage protection enabled, resistor braking disabled
2: Stall overvoltage protection disabled, resistor braking enabled
42/91