Code Name Setting range Default Min. Attri.
C2.21 Torque boost setting
0.0 %: Automatic boost
0.1...20.0 %: Manual boost
DOM 0.1 Run
C2.22 Automatic torque boost factor 0...320 % 50 1 Run
C2.23
Heavy load stabilization
setting
0: Inactive
1: Active
1 Run
C2.24
Light load oscillation damping
factor
0...5,000 % 300 1 Run
C2.25
Light load oscillation damping
filter factor
10...2,000 % 30 1 Run
C2.40 Current limitation mode
0: Always inactive
1: Inactive at constant speed
2: Active at constant speed
2 Stop
C2.42
Current limitation level
[C0.27]...250 % 150 1 Stop
C2.43
Current limitation proportional
gain
0.000...10.000 DOM 0.001 Stop
C2.44
Current limitation
integral time
0.001...10.000 DOM 0.001 Stop
: percentage of motor rated voltage [C1.06].
: percentage of frequency converter rated current.
Rexroth Frequency Converter VFC
3610 / VFC 5610
47/91
Start-up
R912005518_Edition 16 Bosch Rexroth AG