Code Name Setting range Default Min. Attri.
E1.75 Input curve 2 minimum 0.0 %...[E1.77] 0.0 0.1 Run
E1.76 Input curve 2 minimum frequency 0.00...[E0.09] Hz 0.00 0.01 Run
E1.77 Input curve 2 maximum [E1.75]...100.0 % 100.0 0.1 Run
E1.78 Input curve 2 maximum frequency 0.00...[E0.09] Hz 50.00 0.01 Run
Setting range of E1.00...E1.04:
0: Inactive
1: Multi-speed control input 1
2: Multi-speed control input 2
3: Multi-speed control input 3
4: Multi-speed control input 4
10: Acceleration / deceleration time 1 activation
11: Acceleration / deceleration time 2 activation
12: Acceleration / deceleration time 3 activation
15: Freewheeling stop activation
16: Stop DC-braking activation
20: Frequency Up command
21: Frequency Down command
22: Up / Down command reset
23: Torque / speed control switch
25: 3-wire control
26: Simple PLC stop
27: Simple PLC pause
30: Second frequency setting source activation
31: Second run command source activation
32: Error signal N.O. contact input
33: Error signal N.C. contact input
34: Error reset
35: Forward running (FWD)
36: Reverse running (REV)
37: Forward jog
38: Reverse jog
39: Counter input
40: Counter reset
41: PID deactivation
Rexroth Frequency Converter VFC
3610 / VFC 5610
55/91
Start-up
R912005518_Edition 16 Bosch Rexroth AG