REYMSA COOLING TOWERS, INC.
www.reymsa.com
68
D.1 TOWER MAINTENANCE SCHEDULE
Table D-1: Recommended Tower and optional equipment maintenance schedule
REYMSA Cooling TowerS - MAINTENANCE SCHEDULE
PROCEDURE FREQUENCY
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
Inspection for:
-Unusual noises
-Vibration
-Water leakage
-Excessive drift
Monthly
Check fan and inlet
louvers
Monthly
Check water quality
for biological
contaminants contact
your water treatment
service
Quarterly
Basin, Tower Body,
fan inspection and
cleaning
Yearly
Water treatment
control
Monthly
Clean the strainers Monthly
Gear reducer:
Initial oil change
After 500 hours
or four weeks
of operation
Gear reducer:
Check oil level
Weekly
Gear reducer:
Change oil
Every Six Months
or 2500 hours
of operation
Drive Shaft
Rechecking bolt 24
hours after initial
tihghtening may be
necessary
REYMSA Cooling TowerS - OPTIONAL ACCESSORIES
PROCEDURE FREQUENCY
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
Basin heater
inspection for scale
build-up and clean
electrode ends and
junctions box
Quarterly
Electric water level
control inspect
and cleaning all
components
Quarterly
Vibration switch
enclosure for loose
wiring and moisture
and adjust sensitivity
Quarterly
Ladders and handrail
corrosion and screw
loose
Yearly