‐104‐
LOCK: Indicates inhibition of the UPS or a component. A lock is normally preceded by an alarm. In the event of a fault
and consequential inverter lock, the inverter will switch off and power to the load via the bypass line (this procedure is
excluded for locks caused by serious and persistent overloads and for those caused by a short circuit).
CODE DESCRIPTION
L01 Incorrect auxiliary power supply
L02 Disconnection of one or more internal cables
L03 Phase1 input fuse broken or input switch jammed (does not close)
L04 Phase2 input fuse broken or input switch jammed (does not close)
L05 Phase3 input fuse broken or input switch jammed (does not close)
L06 Positive BOOST stage overvoltage
L07 Negative BOOST stage overvoltage
L08 Positive BOOST stage undervoltage
L09 Negative BOOST stage undervoltage
L10 Static bypass switch fault
L11 L1 bypass output locked
L12 L2 bypass output locked
L13 L3 bypass output locked
L14 Phase1 inverter overvoltage
L15 Phase2 inverter overvoltage
L16 Phase3 inverter overvoltage
L17 Phase1 inverter undervoltage
L18 Phase2 inverter undervoltage
L19 Phase3 inverter undervoltage
L20 Continuous voltage on inverter output or Phase1 sinusoid inverter deformed
L21 Continuous voltage on inverter output or Phase2 sinusoid inverter deformed
L22 Continuous voltage on inverter output or Phase3 sinusoid inverter deformed
L23 Phase1 output overload
L24 Phase2 output overload
L25 Phase3 output overload
L26 Phase1 output short-circuit
L27 Phase2 output short-circuit
L28 Phase3 output short-circuit
// L32 Parallel synchronization error
// L33 Parallel synchronization signal fault
L34 Phase1 dissipator overtemperature
L35 Phase2 dissipator overtemperature
L36 Phase3 dissipator overtemperature
L37 Battery charger overtemperature
L38
Phase1 dissipator temperature sensor fault
L39 Phase2 dissipator temperature sensor fault
L40 Phase3 dissipator temperature sensor fault
L41 Battery charger temperature sensor fault
L42 BOOST 1 battery fuse broken
L43 BOOST 2 battery fuse broken
L44 BOOST 3 battery fuse broken
// L45 Parallel bus separation
// L46 Parallel communication fault
// L47 Parallel board fault
LXX IGBT desaturation protection tripped
// = Parallel Lock

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Riello UPS Multi Sentry 160 MST and is the answer not in the manual?

Riello UPS Multi Sentry 160 MST Specifications

General IconGeneral
BrandRiello UPS
ModelMulti Sentry 160 MST
CategoryUPS
LanguageEnglish

Related product manuals