‐83‐
FIRST START-UP AND INITIAL SETTINGS
CAUTION:
Only the following switches can be handled: SWIN, SWBYP, SWOUT, external UPS battery line switch and,
necessary, SWMB (see paragraph “Manual bypass (SWMB)”)
Visual connection inspection
Check that all connections are compliant with the specifications of the “Installation Instructions”
Check that all switches are open
Closing the external battery line switch/fuse
Check the polarity of the connections, then close the external battery line switch/fuses
CAUTION: any connection not compliant with the "Installation Instructions" may damage the battery fuses
and other protections; in this case, call for assistance to avoid further damage to the UPS.
UPS power
Close the UPS's upline protections.
Closing the SWMB Manual bypass switch
Close the SWMB manual bypass switch and check that output voltage is present.
Re-open the SWMB switch.
Closing the input switches
Close the SWIN and SWBYP input switches.