‐71‐
ELECTRICAL CONNECTIONS
CABLE SIZES
For further information, refer to the included “Installation Instructions
PRELIMINARY OPERATIONS FOR CONNECTION
The following operations are to be performed with the UPS disconnected from the power mains, off and with
all equipment switches open. Before making the connection, open all machine switches and verify that the
UPS is completely isolated from its power sources: AC mains and battery. In particular, check that:
- the UPS input line is completely disconnected
- the separate bypass line (if present) is completely disconnected;
- the external UPS battery line switch/fuses are open
- all UPS switches: SWIN, SWBYP, SWOUT and SWMB in the open position
- check with a Multimeter that there are no dangerous voltages
The first connection to be made is the protective conductor (earth wire), to be connected to the screw
marked PE. The UPS must operate while connected to the earthing system.
The input Neutral must always be connected.
CAUTION: a three-phase 4 wire distribution system is required.
The standard UPS version must be connected to a 3 Phase + Neutral + PE (ground protection) TT, TN or IT
type power line. Comply with the phase rotation specification.
TRANSFORMER BOXES (optional) are available to convert distribution systems from 3-wire to 4-wire.
CAUTION: in the event of non-linear three-phase loads, the Neutral conductor (N) current can reach a value
up to 1.7 times that of the phase current. Properly size the Input/output Neutral line keeping this fact in mind.
Carefully read instructions contained in the Battery Box manual before connecting batteries.
Check that battery voltage is the same as allowed by the UPS (consult the Battery Box data plate and the
UPS manual)
CAUTION: the maximum length of the connection cables to the Battery Box is 10 metres