‐75‐
Separate bypass on separate lines:
If the separate bypass input option is present, all protective devices will have to be placed both on the main supply line and on
the line dedicated to the bypass.
Note: the input line and bypass line neutral are shared inside the device; therefore, they will have to be connected to the same
potential. If the two power supplies are different, you must use an isolation transformer on one of the inputs.
UPS without neutral connectivity variation and with separate bypass input connected on an independent power
line
UPS with separate bypass input connected on an independent power line and with galvanic input insulation
UPS with separate bypass input connected on an independent power line and with galvanic output insulation