Commissioning and Maintenance
© robatherm 33
Pos: 48.11 /Inbetri ebnahme und Wartung/_W artung @ 0\mod_12579295852 57_2008.doc @ 2117 @ 3
Maintenance
Pos: 48.12 /Inbetri ebnahme und Wartung/W artungsintervall_3 Monate/ATEX monatlic h @ 0\mod_1257930528679_2 008.doc @ 2122 @ 4
Maintenance Interval
Every three months. ATEX units every month.
Pos: 48.13 /Sicher heitshinweise/!Vor sicht_Sicherheits hinweise beachten_ Querverweis @ 0\mod_12577 77093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 48.14 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_heiße Fläc hen @ 0\mod_125837342198 8_2008.doc @ 2158 @
Caution
To avoid burns, do not touch hot surfaces.
Pos: 48.15 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Temper ieren auf Umgebungstemper atur @ 0\mod_1258373503 611_2008.doc @ 2159 @
Caution
Before starting work allow components to cool/warm up to the ambient temperature.
Pos: 48.16 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Kontakt mit Sole @ 0\mod_1258373184 697_2008.doc @ 2156 @
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Pos: 48.17 /Inbetri ebnahme und Wartung/Luft erwärmer/Lufter wärmer_Wartung @ 0\mod_125 8375212161_2008.doc @ 2166 @
Heating Coil – Periodic Maintenance
Check heating coil for hygiene, contamination on air side, damage, leaks and corrosion
Vent heating coil
Check inlet/outlet for function
Check frost protection for function (determine anti-freeze concentration or thermostat by
means of cooling spray)
Heating Coil – Maintenance when necessary
Clean the heating coil on the air side (see below), rectify damage, leakage and corrosion
Pos: 48.18 /Inbetri ebnahme und Wartung/Luft erwärmer/Lufter wärmer_Reinigung @ 0\mod _1258375355516_2008.d oc @ 2167 @ 44
Cleaning
Clean coils already assembled or if not accessible pull them out for cleaning. Contamination
which has been removed must not enter adjoining unit parts. Remove dirt and contaminated
water carefully.
Observe the following points:
Avoid bending plate fins
Blow out with compressed air in the opposite direction
Do not use a high pressure cleaner or a high pressure steam cleaner
Clean with water and low pressure
Cleaning Agents
Use cleaning agents with a pH-value between 7 and 9 if required.
Pos: 48.19 /Inbetri ebnahme und Wartung/IBN&W artung_Lufterwär merund-kühler_W artung_Außerbetriebse tzung @ 0\mod_12613912661 77_2008.doc @ 2282 @ 44
Shut Down
If out of operation for some time, especially if there is a danger of freezing, the heat
exchanger must be emptied completely if no anti-freezing agent was added. For this purpose
remove all purging and discharging screws. Then for complete emptying blow air
(compressed air, fan etc) through each heat exchanger as up to 50% fluid may remain in the
heat exchanger during free purging which results in a higher danger of damage during frost.
Remove brine following manufacturer information.