Configure FLEX I/O Digital Modules on a DeviceNet Network        Chapter 5
Set the status size for a scanner
If you want this information: Set the Status 
Size to (DINTs):
Which gives you:
Member: Data Type
count of I/O scans 10 ScanCounter DINT
indication that a device has failed:
•There is 1 bit for each address on the DeviceNet network (0 -63).
•The position of a bit = address of a device.
•If a bit = 1, then the device at that address has failed.
DeviceFailureRegister SINT[8]
indication that the data size of a device does not match the amount of 
memory that is allocated for the device in the scanner:
•There is 1 bit for each address on the DeviceNet network (0 -63).
•The position of a bit = address of a device.
•If a bit = 1, then their is a mismatch with that address.
AutoverifyFailureRegister SINT[8]
indication that a device is idle:
•There is 1 bit for each address on the DeviceNet network (0 -63).
•The position of a bit = address of a device.
•If a bit = 1, then the device at that address is idle.
DeviceIdleRegister SINT[8]
indication that a device is online:
•There is 1 bit for each address on the DeviceNet network (0 -63).
•The position of a bit = address of a device.
•If a bit = 1, then the device at that address is online.
ActiveNodeRegister SINT[8]
ASCII representation of scanner status/display StatusDisplay SINT[4]
address of the scanner 11 ScannerAddress SINT
status code of scanner ScannerStatus SINT
address with an error:
•scrolls through the addresses with errors
•ScrollingDeviceStatus member shows the status code
ScrollingDeviceAddress SINT
status code of an address with an error:
•scrolls through addresses with errors
•ScrollingDeviceAddress member shows the address
ScrollingDeviceStatus SINT
possible future expansion of the structure – 5 DINTs 16
status code of lower 32 devices – 1 byte per device 24 DeviceStatus SINT[32]
status code of all devices – 1 byte per device 32 DeviceStatus SINT[64]