Rockwell Automation Publication 7000L-UM301F-EN-P - March 2020 409
Component Definition and Maintenance Chapter 5
If there were any changes to the motor, input transformer, or associated
cabling, you will have to retune the drive to the new configuration using
autotuning.
Save all parameter changes (if any) to NVRAM.
Run the application up to full speed/full load, or to customer satisfaction.
Capture the drive variables while running, in the highest access level if
possible.
Additional Tasks During Preventive Maintenance
Investigation of customer’s concerns relating to drive performance
Relate any problems found during above procedures to customer issues.
Informal instruction on drive operation and maintenance for plant
maintenance personnel
Reminder of safety practices and interlocks on MV equipment, and on
specific operating concerns
Reminder of the need to properly identify operating conditions
Recommendation for critical spare parts which should be stocked in-plant
to reduce production downtime
Gather information on all spare parts on site, and compare that with
factory-recommended critical spares to evaluate whether levels are
sufficient.
Contact MV Spare Parts group for more information.
Vacuum Bottle Integrity Testing using a Vacuum Checker or AC Hipot
Refer to Publications 1502-UM050_EN-P (Series D) and 1502-
UM052_-EN-P (Series E) for a detailed description of all 400A
contactor maintenance.
Final Reporting
A complete, detailed report on all steps in the Preventive Maintenance
procedures should be recorded to identify changes.
A completed copy of this checklist should be included.
A detailed description of ALL ADJUSTMENTS AND
MEASUREMENTS that were taken during the process should be
included in an addendum (Interlock Adjustments, Loose Connections,
Voltage Readings, Megger Results, Parameters, etc.)
THIS INFORMATION SHOULD BE COMMUNICATED TO MV
PRODUCT SUPPORT SO THAT FUTURE SUPPORT
ACTIVITIES WILL HAVE THE LATEST SITE INFORMATION
AVA IL A BL E.
This can be faxed to (519) 740-4756