EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerFlex 7000

Rockwell Automation Allen-Bradley PowerFlex 7000
434 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 7000L-UM301F-EN-P - March 2020 261
Commissioning Chapter 4
Synchronous Transfer
When commissioning a drive employing synchronous transfer, the following
waveforms should be captured and submitted with the commissioning package.
Refer to the “Synchronous Transfer Commissioning Guidelines” for a detailed
commissioning procedure.
While measuring the bypass (BP) contactor closing time:
Capture 120V bypass close command from the BP Contactor Close
output (J1-12) at the ACB (refer to electrical drawing for specific wire/
terminal number).
Capture the 9V signal across the bypass contactor vacuum bottles (refer to
the tech note PowerFlex 7000_GEN-78 for details).
Label the waveforms as “BP_Close_Cmd” and “Actual_Closure”.
Save the worksheet as “Bypass Contactor Close Delay”.
Table 17 - Oscilloscope Setting
Figure 217 - Sample Waveforms
Ch1: Bypass Contactor Close Command (BPC output at ACB, J1-12 & 402)
Ch2: Actual Closure of Bypass Contactor (using 9V battery across contactor vacuum bottles)
While simulating a synchronous transfer to determine the best lead angle:
Make sure the Diagnostic Trend has been setup and is armed.
Capture motor voltage at ACB test point “Vu v ” & bypass voltage at ACB
test point “Vu v s ”.
Oscilloscope Time Base Waveform Test-Point Waveform Label
Ch. 1 25ms/div. BP Contactor Close
Command
BP Contactor Close
Cmd
BP_Close_Cmd
Ch. 2 Actual Closure of BP Across 2K-Ohm
resistor connected in
series with 9V
battery
Actual_Closure

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 7000

Related product manuals