120 Rockwell Automation Publication 20D-PM001D-EN-P - March 2019
Chapter 2 Programming and Parameters
1000 UserFunct Enable
This parameter is used to enable and disable the optional user functions. If a bit is set the corresponding function in enabled. If the bit is not set the corresponding function is disabled and will not
be processed (outputs will not be updated).
Notes: Bit 16 “Ratio Calc” was added for firmware version 2.004. Bit 5 “AddSub Math” and bit 6 “Delay Timer” were added for firmware version 3.001. Bit 7 “EGR” (Electronic Gear Ratio) was added
for firmware version 4.001.
1001 UserFunct Actual
This parameter displays the actual status of the user functions. If a bit is set, then the corresponding function is active. When Par 1001 [UserFunct Actual] does not match Par 1000 [UserFunct Enable]
it is an indication that the function could not activate because of an error. Typically, the limitation is caused by processor overloading. Adjust Par
146 [FW TaskTime Sel] to a slower task cycle (more
time).
1002
to
1011
UserData DInt 01
to
UserData DInt 10
These are general purpose parameters available for storage of 32-bit enumerated data or DInt data by the user.
These parameters will be retained through power cycles.
Default:
Min/Max:
0
-/+2147483648
Y
RW 32-bit
Integer
1012
to
1021
User Data Real 01
to
UserData Real 10
These are general purpose parameters available for storage of Real data by the user. These parameters will be
retained through power cycles.
Default:
Min/Max:
0.0000
-/+2200000000.0000
Y
RW Real
1022 Sel Switch Ctrl
This is the control parameter for the switches used by the Selector Switch user functions. 16 Input Selector Switches (Pars 1029 - 1044) are controlled by bits 1-4.
• Bit 0 “SSW DataPass” Updates the output. If bit 0 is low, the output is NOT updated with the selected input.
• Bits 1 “Sel Swtch 00” - 4 “Sel Swtch 03” Binary coded selection of the 16 inputs to the switch. Bit 1 is the Least Significant Bit. If these bits are all low (set to “0”), Par 1029 is selected. If these bits
are all high (set to “1”) Par 1044 is selected. (Refer to Pars 1029
- 1044.) The values in these bits can be controlled by the digital inputs. (Refer to Pars 825 - 830 and to the “Selector Switches”
section of the PowerFlex 700S Drives with Phase II Control - Reference Manual, publication PFLEX-RM003, for more information.)
• Bit 5 “SW Real 1 On” activates the Real switch. (Refer to Pars 1023
- 1025.)
• Bit 6 “SW DInt 1 On” activates the DInt switch. (Refer to Pars 1026 - 1028.)
1023 Swtch Real 1 NC
This is the Normally Closed input to the Real switch. When Par 1022 [Sel Switch Ctrl], bit 5 “SW Real 1 On” is low,
this input is updated to Par
1025 [Swtch Real 1 Output].
Default:
Min/Max:
0.0000
-/+2200000000.0000
Y
RW Real
1024 Swtch Real 1 NO
This is the Normally Open input to the Real switch. When Par 1022 [Sel Switch Ctrl], bit 5 “SW Real 1 On” is high,
this input is updated to Par 1025 [Swtch Real 1 Output].
Default:
Min/Max:
0.0000
-/+2200000000.0000
Y
RW Real
1025 Swtch Real 1 Out
This is the result of the Real switch. The output is loaded with the selected input based on Par 1022 [Sel Switch
Ctrl], bit 5 “SW Real 1 On”. If this parameter does not update, check the setting of Par
1000 [UserFunct Enable], bit
1 “User Params”.
Default:
Min/Max:
0.0000
-/+2200000000.0000
RO Real
1026 Swtch DInt 1 NC
This is the Normally Closed input to the DInt switch. When Par 1022 [Sel Switch Ctrl], bit 6 “SW DInt 1 On” is low,
this input is updated to Par
1028 [Swtch DInt 1 Output].
Default:
Min/Max:
0.0000
-/+2200000000.0000
Y
RW 32-bit
Integer
1027 Swtch DInt 1 NO
This is the Normally Open input to the Real switch. When Par 1022 [Sel Switch Ctrl], bit 6 “SW DInt 1 On” is high,
this input is updated to Par
1028 [Swtch DInt 1 Output].
Default:
Min/Max:
0.0000
-/+2200000000.0000
Y
RW 32-bit
Integer
No. Name
Description
Values
Linkable
Read-Write
Data Type
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
MOP
Ratio Calc
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
EGR
Delay Timer
AddSub Math
MulDiv Math
Logic Functs
Converts
Sel Switches
User Params
Default xxxxxxxxxxxxxx10xxxxxxxx01111111
Bit 313029282726252423222120191817161514131211109876543210
0 = False
1 = True
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
MOP
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
MulDiv Math
Logic Functs
Converts
Sel Switches
User Params
Default xxxxxxxxxxxxxx0xxxxxxxxxxxx00000
Bit 313029282726252423222120191817161514131211109876543210
0 = False
1 = True
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
SW DInt 1 On
SW Real 1 On
Sel Swtch 03
Sel Swtch 02
Sel Swtch 01
Sel Swtch 00
SSW DataPass
Default xxxxxxxxx0000000
Bit 1514131211109876543210
0 = False
1 = True