Appendix C Specifications
Table 44 - Kinetix 5300 (230V, three-phase) Input Power Specifications
Attribute 2198-C2030-ERS 2198-C2055-ERS 2198-C2075-ERS
AC input voltage 170…253V rms, three-phase (230V nom)
AC input frequency 47…63 Hz
Main AC input current (rms)
(1)
15.18 A 31.13 A 36.93 A
Max inrush current (0-pk) 7.4 A 14.8 A 14.8 A
Peak AC input current (rms) 41.26 A 73.06 A 86.25 A
Control power input voltage
(2)
21.6…26.4V DC
24V DC nom
Control power input current
(1)
(3)
(non-brake motors)
0.9 A
DC
1.7 A
DC
1.7 A
DC
Continuous output current (rms) 19.6 A 40.2 A 47.7 A
Continuous output current (0-pk) 27.7 A 56.9 A 67.5 A
Peak output current (rms)
(4)
61.0 A 108.0 A 127.5 A
Peak output current (0-pk) 86.3 A 152.7 A 180.3 A
Line loss ride through 20 ms
Continuous output power 5.02 kW 10.30 kW 12.22 kW
Internal shunt on 387.5V
Internal shunt off 377.5V
Internal shunt resistor 60 Ω 40 Ω
Internal shunt power 50 W 75 W
Bus undervoltage limit 144V
Bus overvoltage limit 405V
Bus capacitance 1680 µF 2460 µF 3280 µF
Capacitive energy absorption 30.25 J 44.29 J 59.05 J
Efficiency 97%
Short-circuit current rating 200,000 A (rms) symmetrical
(1) Drives are limited to one power cycle per minute.
(2) The cooling fan runs as part of the control power startup routine, when the inverter is enabled, and if the inverter temperature exceeds preset threshold.
(3) For current values when motors include a holding brake, refer to Kinetix 5300 Servo Drive Control Power Specifications.
(4) Peak RMS current allowed for up to 1.0 seconds.