62 Rockwell Automation Publication 2198-RM006A-EN-P - December 2020
Appendix C Specifications
Table 45 - Kinetix 5300 (480V, three-phase) Input Power Specifications
Attribute 2198-C4004-ERS 2198-C4007-ERS 2198-C4015-ERS 2198-C4020-ERS
AC input voltage 342…528V rms, three-phase (480V nom)
AC input frequency 47…63 Hz
Main AC input current (rms)
(1)
1.24 A 2.25 A 4.03 A 5.65 A
Max inrush current (0-pk) 15.5 A 15.5 A 15.5 A 15.5 A
Peak AC input current (rms) 3.59 A 6.29 A 12.18 A 16.10 A
Control power input voltage
(2)
21.6…26.4V DC
24V DC nom
Control power input current
(1)
(3)
(non-brake motors)
0.4 A
DC
0.4 A
DC
0.9 A
DC
0.9 A
DC
Continuous output current (rms) 1.6 A 2.9 A 5.2 A 7.3 A
Continuous output current (0-pk) 2.3 A 4.1 A 7.4 A 10.3 A
Peak output current (rms)
(4)
5.3 A9.3 A18.0 A23.8 A
Peak output current (0-pk) 7.5 A 13.2 A 25.5 A 33.7 A
Line loss ride through 20 ms
Continuous output power 0.86 kW 1.55 kW 2.78 kW 3.90 kW
Internal shunt on 775V
Internal shunt off 765V
Internal shunt resistor 100 Ω 100 Ω 60 Ω 60 Ω
Internal shunt power 30 W 30 W 50 W 50 W
Bus undervoltage limit 275V
Bus overvoltage limit 810V
Bus capacitance 165 µF 165 µF 280 µF 330 µF
Capacitive energy absorption 8.13 J 13.79 J 16.26 J
Efficiency 97%
Short-circuit current rating 200,000 A (rms) symmetrical
(1) Drives are limited to one power cycle per minute.
(2) The cooling fan runs as part of the control power startup routine, when the inverter is enabled, and if the inverter temperature exceeds preset threshold.
(3) For current values when motors include a holding brake, refer to Kinetix 5300 Servo Drive Control Power Specifications
.
(4) Peak RMS current allowed for up to 1.0 seconds.